Stop Burning Diesel Into Resistors in Germany

Project Overview

BESS as Generator Test Load In Germany refers to a landmark FFD POWER project tailored for diesel generator manufacturers across Germany. This innovative solution deploys a controllable battery energy storage system (BESS) as a test load for generator testing, replacing traditional resistor load banks that simply dissipate test power as wasted heat. Instead of discarding power output during generator performance verification, the BESS stores captured electricity for multi-purpose utilization: excess energy can be exported back to the public grid, leveraged for peak-valley arbitrage to cut operational costs, or retained as reliable on-site backup power for facility emergencies as needed.

BESS as Generator Test Load In Germany FFD POWER battery energy storage system for diesel generator testing instead of resistor load banks
BESS as Generator Test Load In Germany FFD POWER energy storage test load

Project Background

Diesel generators must be tested under real electrical load before delivery or commissioning. For a generator supplier, the conventional resistor load-bank method is technically simple but economically wasteful: diesel is burned, electricity is produced, and the output is immediately converted into heat. The customer needed a test-load solution that preserved the testing function while turning recoverable energy into a usable asset.

Project Challenge

FFD POWER Solution

FFD POWER supplied a 500kW / 1.044MWh BESS based on four Galaxy261L battery cabinets. The system uses separated PCS logic: one side absorbs diesel generator output as a rectifier/load path, while the grid-side PCS handles bidirectional grid interaction for export, import, arbitrage, and backup dispatch.

System Specifications

Operational Logic: The Energy Bank" Effect

The core innovation lies in how the EMS manages generator testing, energy storage, and grid interaction within one site-level control strategy: